.+/-10% fluctuations
Cost Savings
Better asset life
Less heating
Less risk of heating
System concept
System concept
modular
Rated power 300 kVA*
Nominal network voltage 400 V / 480 V / 220 V*
Rated frequency 50/60 Hz ± 5 %
Network configuration 3-phase, TN
Grid short circuit power scalable
Correction range 40 % for 30 s ± 10 % continuously
Single-phase dips from 40 % UN to 100 % UN for 30 s
Three-phase dips from 60 % UN to 100 % UN for 30 s
from 50 % UN to   90 % UN for 20 s
Overload capability 150 % IN (30 s)
Overload in bypass-mode 35 kA / 10 ms
Accuracy of the output voltage ≤ ± 1 %
Accuracy during voltage dips ± 3 %
Reaction time 220 µs
Transient time < halfwave
System efficiency > 98 %
Communication Ethernet (RJ45) / FTP-Server / Mail-Server
Parametrization/Analysis touch panel / Log-SD-Card / Mail
Degree of protection IP 20D*
Ambient temperature 0 °C (min.), 40 °C (max.)
Dimensions (w x d x h) 600 x 800 x 2282 mm (incl. socket)
Weight 900 kg
Power connection from the bottom, from the side, from behind,
Busbar connection with additional side cabinet
Height of connection points incoming 800 mm, outgoing 370 mm
Door hinges right
Options Maintenance bypass for bridging the system,
Measuring device for independent analysis Class A
* Other ratings on request
  Subject to changes